I designed a foundation for a PEMB. I want to know peoples methods for designing the footings for uplift. I have typically designed the footing to weigh as much as the net uplift load (0.6D+(W or 0.7E)). The calculated net uplift force has a factor of safety of 1/0.6 = 1.67 in it from the reduction of the dead load. I received a plan check comment that states that with my calculations there is only a factor of safety of 1. But this is a factor of safety of 1 in regards to the net uplift force. Should we really be increasing the footing weight to maintain a factor of safety = 1.5 over the net uplift force? To me this is more like a factor of safety of 1.67*1.5 = 2.51. Not to mention we know what the actual weight of the footing will be. This is a commercial building and the city inspectors are very good in requiring construction matches the plans, especially foundations. Am I wrong? Do others design PEMB footings that weigh 1.5 times the net uplift force?
Thanks in advance for your replies
Jeff Hedman